CEMP-E
TI 810-32
10 January 2002
NOTE:
PROVIDE A MINIMUM OF 4
CONNECTIONS PER PANEL.
3/8 " NUT-TACK WELD TO PLATE
CONNECTIONS SHALL BE 4 1/2 "
FROM EDGES OF PANELS AND
1/8 " CHECKERED PLATE
10" FROM ENDS OF PANELS.
2" SQ.X4" GALV. WASHER
GALV. STEEL GRATING
3/8 "0X1 1/2 " GALV. BOLT
CONNECTION FOR ATTACHING
CHECKERED PLATE TO GRATING
VARIES
5/16 " ALUMINUM CHECKERED
PLATE IN CONFORMANCE
WITH ANSI H35.1.
PLATE WILL BE SAME
DIMENSION AS GRATING
SECTION IT COVERS
EXTEND ALUMINUM
CHECKERED PLATE
TO COVER BEAM
BLOCKOUTS
CHECKERED PLATES SHALL BE
PROVIDED WITH 12"X12"
VENTILATION OPENINGS AT
CORNERS (TYP.)
NOTE: SPACING BETWEEN PANELS AND BETWEEN
PANELS AND ANGLES SHALL BE 1/4 "
OPEN GRATE COVER W/CHECKER PLATE
CHECKER PLATE COVER DETAILS
NO SCALE
DESIGNER NOTE: CHECKERED PLATE TO BE USED TO COVER GRATING IN COLD CLIMATES
AND AREAS WHERE TRASH ACCUMULATION IS A CONCERN.
Figure 3-18. Detail of Checker Plate Cover.
3-25