Table 4-2. Support spacing schedule
||content|| \ MAXIMUM HORIZONTAL PIPE SUPPORT SPACING FOR STEEL /1/
DISTRIBUTION PIPING
PIPE SIZE
SPACING
(INCHES)
(FEET)
1
7
1-1/4
7
1-1/2
9
2
10
2-1/2
11
3
12
2-1/2
13
4
14
5
16
6
17
8
19
10
22
12
23
14
25
16
27
18
28
20
30
24
32
30
33
NOTES TO THE DESIGNER: These spacings are maximum for horizontal, straight
runs. More closely spaced supports must be provided for bends and risers and at
equipment.