Project Name
Project Number
UEPH Complex
Statement of Work
26 November 2001
the following furnishings: One twin bed with headboard and footboard 102mm x 2083mm [40" x
85"]; one entertainment center for occupant's television and sound system 864mm wide x
635mm deep x 1930mm high [34" x 25" x 76"]; one chest of drawers 712mm wide x 458mm
deep x 661mm high [28" x 18" x 26" high]; one nightstand 485mm wide x 435mm deep x
535mm high [19" x 17" x 21" high]; one desk 1524mm wide x 762 deep (with keyboard tray
retracted) x 762mm high [60" wide x 30" deep x 30" high]; and one desk chair 500mm wide x
535mm deep x 851mm high [19-1/2" x 21" x 33-1/2" high].
Base: wood or resilient cove base
Walls: painted gypsum wallboard or painted veneer plaster
Ceiling: painted gypsum wallboard, painted veneer plaster, or painted underside of precast
concrete structural floor planks
2-2.2.1.5 Other requirements: Living/sleeping room shall have at least one exterior operable
window with insect screen. Window shall meet egress requirements of NFPA 101 and
International Building Code. Window shall not be located adjacent to an exterior corridor or
breezeway. Door between service area and living/sleeping room shall have passage function
(F75) latchset. Door between public corridor and living/sleeping room shall have mortise
dormitory function (F13) lockset. Provide minimum of one combination telephone/data outlet on
in each Living /Sleeping room. Provide minimum of one cable television outlet in each
Living/Sleeping room. Coordinate outlet locations with furniture arrangement. Refer to Chapter
9 Electrical Systems.
Closet. Minimum net area 3 m2 [32.3 sf]. Provide one.
2-2.2.2
2-2.2.2.1
Function: Private walk-in closet for clothing and storage of boxes and field gear.
2-2.2.2.2 Adjacency requirements: Adjacent to Living/sleeping room. Provide minimum
700mm [2'-4"] wide door between living/sleeping room and closet.
2-2.2.2.3 Furnishings/Fixtures/Equipment (FFE): Provide minimum 2 linear meters [6'-7"] of
rod and shelf.
Base: wood or resilient cove base
Walls: painted gypsum wallboard or painted veneer plaster
Ceiling: painted gypsum wallboard, painted veneer plaster, or painted underside of precast
concrete structural floor planks.
2-2.1.2.5 Other requirements: Door shall have privacy function (F76) lockset, or be equipped
with a hasp so the occupant can provide his/her own padlock.
2-2.2.3
Service Area. Provide one per module. Service Area may be a separate room, or
may be integrated into Living/sleeping room as in an efficiency apartment.
2-2.2.3.1
Function: Circulation space, food preparation area, [area for washer and dryer],
and eating area for occupant and visitors.
SOW-9