CEMP-E
TI 810-32
10 January 2002
DRILL THRU 13/16 " DIA. 4 PLACES,
FOR 3/4 " DIA. CONCRETE EXPANSION
4 1/4 "
THREAD LENGTH
ANGLE
4" X 3" X 3/8 " X 4 1/2 "
3
3
1/4
W6 X 20
TYP.
1/4
1/4
PLATE 12" X 3/4 " X 1'-3 1/4 "
SECTION
1
NOTES:
1. PIPING SHALL REST ON THIS PIPE SUPPORT BY
MEANS OF A FREE PIPE SHOE (SUPPORT) AS
DETAILED IN FIG. 4-1. PIPE SHOES SHALL BE
CENTERED ON THE TOP BEAM OF THIS SUPPORT
IN THE COLD CONDITION.
1
5/8J"
1
W6 X 20
4'-0"
18" x 18" x 6"
CONCRETE PAD (TYP.)
3/4 " DIA. X 10" LONG
SLAB REINFORCEMENT
NOT SHOWN FOR
(TYP.)
CLARITY
VALVE AND PIPE SUPPORT
.
SCALE 1 INCH 1 FOOT
=
.
1'
12"
6"
0
Figure 3-4. Typical Valve/Piping Support Detail.
3-11