MIL-HDBK-1003/7
c) 40 CFR Part 60, Subpart Db, Standards of Performance for Industrial-
Commercial-Institutional Steam Generating Unit.
The most stringent of these regulations (Subpart Da) applies to new electric
utility steam generating units and should not be applicable to a military power plant.
The Subpart Db NSPS apply to industrial-commercial-institutional steam
generating units larger than 100 million Btu per hour heat input rate. SO2, NOx and
particulate matter are currently regulated under these regulations. A military power
plant would qualify as an industrial-commercial-institutional steam generating unit.
The Federal NSPS for such units are presented in Table 31.
Table 31
Steam Generating Units Larger Than 100 MBTU/HR Input Rate
+)))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))),
*
*
Maximum
*
*
Emission Rate
*
* Pollutant
Fuel
Special Conditions
lb/MBtu
*
*
* Particulate
*
Coal
Up to 10% annual capacity
0.05
* Matter
*
factor of other fuels
*
*
*
*
Oil
---
0.10
*
*
*
*
Coal & other
Other fuels greater than
0.10
*
*
fuels
10% annual capacity
*
*
factor
*
*
*
*
Wood & other
Annual capacity factor
0.10
*
*
fuels except
greater than 30%
*
*
coal
for wood
*
*
*
*
Wood & other
Annual capacity factor
0.20
*
*
fuels except
greater than 10% but
*
*
coal
less than 30% for wood
*
*
and unit less than 250 MBtu/hr
*
*
*
*
Municipal
Up to 10% annual
0.10
*
*
type solid
capacity factor of
*
*
waste
other fuels
*
*
*
*
.))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))-
193