MIL-HDBK-1003/7
Table 28
Typical Fixed Fire Detection and Suppression Systems
Type of Fire
Suppression
Location
System
Type of Detection
Operation
Administration
Wet pipe
Fixed temperature
Automatic
Area (excluding
sprinkler
quartzoid bulb
Plans and records
NFPA or DOD
Cross-zoned
Automatic
storage room
approved
ionization and
photo-electric smoke
detection system
Control room (below
Not applicable
Ionization smoke
Alarm only
ceiling)
detection
Control room (above
Not applicable
Ionization smoke
Alarm only
ceiling)
detection
Control room (main
Not applicable
Ionization smoke
Alarm only
control panel)
detection
Control equipment
NFPA or DOD
Cross-zoned
Automatic
room
approved
ionization and
photo-electric
Cable spreading room
Wet pipe
Fixed temperature
Automatic
sprinkler
quartzoid bulb
--
Ionization smoke
Alarm only
detection
Turbine underfloor
Dry pipe
Fixed temperature
Automatic
area, grade and
sprinklers
quartzoid bulb
mezzanine level
Preaction
Fixed temperature
Manual
spray
Boiler feed pump
Deluge
Dry pilot
Automatic
turbine
spray
SUPERSEDES PAGE 173 OF MIL-HDBK-1003/7.