MIL-HDBK-1004/5
system with a 100-ampere unit load for this case. Since the system is linear,
the system voltage conditions can be calculated for more unit-loaded
utilization service assemblies.
Figure A-1
5,000-Foot Feeder Cable-Case A-1
While the schematic (Figure A-1, for example) shows only one
utilization service assembly on the feeder at bus 3, the remaining utilization
service assemblies can be included by assuming that all utilization service
assemblies for the feeder connect to bus 3 (see Table A-1). This will produce
the largest steady-state voltage drop. The error introduced will not change
the results. Analysis indicates that voltage at bus 3, when the last
39