MIL-HDBK-1004/5
Table A-5
90-kVA Line Drop Compensator's Per-Unit Voltage Increase (1)
___________________________________________________________
Line Drop
Low-Voltage
Compensation
Increase
Percent
Per-Unit Volts
____________________________________________________________
12
0.0428
14
0.0497
16
0.0548
18
0.0609
20
0.0646
____________________________________________________________
(1) Parameters are:
15,000-foot feeder cable
200-foot service cable
40-foot aircraft cable and
100-ampere, 0.8-power-factor unit loads
64