ANSI/IEEE 484, IEEE Recommended Practice for Installation Design and
Installation of Vented Lead-Acid Batteries for Stationary Applications.
ANSI/IEEE 1106, IEEE Recommended Practice for Maintenance, Testing,
and Replacement of Vented Nickel-Cadmium Batteries for Stationary
Applications.
IEEE 1187, IEEE Recommended Practice for Installation Design and
Installation of Valve Regulated Lead-Acid Batteries for Stationary
Applications.
IEEE 1188, IEEE Recommended Practice for Maintenance, Testing and
Replacement of Valve Regulated Lead-Acid Batteries for Stationary
Applications.
9-8.1.3 In addition to substation applications, the requirements of this section apply to
all stationary battery applications, including engine starting, UPS, and other backup
power applications.
9-8.2
Protective Equipment. The following equipment must be available for the
safe handling of the battery and protection of personnel:
Safety glasses with side shields, goggles, and/or face shields
Acid-resistant gloves
Protective aprons and safety shoes
Portable or stationary water facilities for rinsing eyes and skin in case of
contact with acid electrolyte
Class C fire extinguisher
For lead acid batteries, bicarbonate of soda to neutralize any acid spillage
(1 lb/gal or 0.1 kg/L of water)
Adequately insulated tools
Lifting devices of adequate capacity, when required