UFC 3-560-01
6 December 2006
Including change 1, 7 December 2006
Table 10-7. Insulating Aerial Ladders and Insulating Vertical Aerial Towers
60 Hertz (rms) Test
Direct Current Test
Maximum
Maximum Allowable
Unit Rating
Voltage
Voltage
Allowable
Time
Current
Current
46 kV &
40 kV
400
1
56
3
below
(rms)
microamperes minute 56 kV microamperes minutes
20kV and
20 kV
200
1
28
3
below
(rms)
microamperes minute 28 kV microamperes minutes
Table 10-8. In Field Tests for Insulating Aerial Devices
ANSI/SIA A92.2 Section 5.4.3.2 Item 10(c)
Aerial Device
Maximum Allowable
AC Voltage
Time of Test
Category
Current
A or B
Line to Ground
1 milliampere/kVAC
3 minutes
A or B
Line to Ground
.5 microamperes/kVAC
3 minutes
Note: This test may be used as a Periodic Test when the voltage is at least
double that of any circuit on which the aerial device is to be used, but not
exceeded the Qualifications Voltage of the aerial device.
||content||
\ 10.14.1.6.1 All records for the annual and frequent inspections documentation shall
be retained for a period of at least three years for Manually Propelled Elevating Aerial
Platforms (ANSI/SIA A92.3), Boom Supported Elevating Work Platforms (ANSI/SIA
A92.5), and Self-Propelled Elevating Work Platforms (ANSI/SIA A92.6). Written, dated
and signed inspection and periodic test reports and records shall be retained for five
years for Vehicle-Mounted Elevating and Rotating Aerial Devices as required by
ANSI/SIA A92.2./1/
10-14.2
General Requirements.
10-14.2.1 Lift controls must be tested each day prior to use if the lift is to be used that
day, to determine if the controls are in safe working condition. Lift controls must be
tested on a monthly basis when not in use.
10-14.2.2 Do not alter the insulated portion of an aerial lift in any manner that might
reduce its insulating value.
10-14.2.3 Ensure the manufacturer's operation manual is available with any aerial lift.
10-39