UFC 3-580-10
14 July 2004
Including changes 12 April 2005
DHTB1& DHTB2 TRANSPORT BOUNDARY CABINETS - EXT UPS-(Two - 3 Ton A/C units)
VOLT
CABINET EQUIPMENT AMPS
SITE COOLING AMPS
FEEDER AMPS
TPP FEEDER
COOLING
Heat to
MODE
BK
(VOLT/Phase)
Phase A/B/C
Phase A/B/C
Phase A/B/C
Wire Size
Room
AMP/POLE
(Btu/hr)
208Y120 3 PH
100/3
4 #3, #8 G, 1.25"C
24,813
NORMAL
17
50
67
DCTB1 AND DCTB 2 CLASSIFIED TRANSPORT BOUNDARY [Two - 1 Ton A/C units ] EXT. UPS
VOLT
CABINET EQUIPMENT AMPS
SITE COOLING AMPS
FEEDER AMPS
TPP FEEDER
COOLING
Heat to
MODE
BK
Wire Size
(VOLT/Phase)
Phase A
Phase B
Phase A
Phase B
Phase A
Phase B
Room
AMP/POLE
(Btu/hr)
120/208/1 PH.
50/2
3#8, #10 G, 1"C
11,717
NORMAL
11
11
20
20
31
31
DPOP 16-SERVER CABINET 1 (1701 to 5000 Seats) [One 2-Ton A/C unit ]
VOLT
CABINET EQUIPMENT AMPS
SITE COOLING AMPS
FEEDER AMPS
TPP FEEDER
COOLING
Heat to
MODE
BK
Wire Size
(VOLT/Phase)
Phase A
Phase B
Phase A
Phase B
Phase A
Phase B
Room
AMP/POLE
(Btu/hr)
120/208/1 PH.
NORMAL
33
17
29
29
61
46
100/2
3#3, #8 G, 1"C
19,853
120/208/1 PH.
UPS FAILURE
48
2
29
29
77
30
60