UFC 3-600-01
26 September 2006
4-11.2.1
Provide stand-alone (not dependent upon the building fire alarm
system for operation) control panels that are listed for releasing device service
and monitored by the building fire alarm system.
4-11.2.2
Careful consideration must be given to compartment under/over-
Pressure relieving vents, located near the finished ceiling, may be necessary to
regulate rapid pressure changes during discharge. Comply with the
manufacturer's recommended procedures relative to enclosure venting.
4-11.2.3
Provide a manually activated exhaust system to facilitate the
extraction of any remaining clean agent after the required hold time of the total
HVAC system for the enclosure.
4-12
WATER MIST FIRE PROTECTION SYSTEMS.
4-12.1
Application.
Water mist fire protection systems are suitable for protection of certain types of
special occupancies, hazards, and facilities. Water mist fire protection systems
are not a substitute for required automatic sprinkler systems.
4-12.2
Design Requirements.
Water mist fire protection systems must conform to NFPA 750, Water Mist Fire
Protection Systems.
4-12.2.1
Provide stand-alone (not dependent upon the building fire alarm
system for operation) control panels that are listed for releasing device service
and monitored by the building fire alarm system.
37