UFC 3-600-01
26 September 2006
Figure 6-5 Townhouse (Attached Single-Family Dwellings)
2-hour fire wall
(structurally
independent)
(typical)
6-2.1.3
Duplex.
A duplex is a stand-alone structure that contains only two (2) dwelling units that
are separated by 1-hour fire resistive construction. See Figure 6-6.
Figure 6-6 Duplex
1 - hour fire
resistive
partition
1 - hour fire resistive
floor
"Side-By-Side"
"Over/Under"
6-2.1.4
Single-Family Detached House.
A single-family detached house is a stand-alone structure that contains one
dwelling unit for a single family.
6-2.2
New Family Housing.
6-2.2.1
Smoke Alarms.
Install hard-wired smoke alarms for all single family and multi-family housing
projects. Smoke alarms must be located in the hallway between the bedroom
areas and the rest of the dwelling unit, and on each additional story of the family
47