UFC 3-600-01
26 September 2006
amounts of flammable liquid, in closed containers are allowable in quantities not
to exceed 75 L (20 gal) per fire area. This classification includes but is not limited
to the following occupancies:
Armories
Sheet metal shops
Bowling alleys
Ship fitting shops
Clubs (officer, enlisted personnel, etc.)
Kitchens and bakery
Small stores
Theaters and auditoriums
Welding shops
Forge shops
Laundries
Automobile parking garage
Electronics assembly and repair
B-1.3
Ordinary Hazard Group 2 Occupancies.
Occupancies or portion of occupancies where quantity and combustibility of
contents is moderate, stockpiles do not exceed 3.7 m (12 ft), and fires with
moderate rate of heat release are expected. Moderate, scattered amounts of
flammable liquids in closed containers are allowable in quantities not to exceed
200 L (50 gal) per fire area. Small amounts of flammable liquids may be
exposed as required by normal operations. This classification includes but is not
limited to the following occupancies:
Exchanges
Aviation Depots
Boiler rooms
Electrical maintenance shops
100