MIL-HDBK-1027/4A
TABLE 2.2 (Continued)
TRAINER FACILITIES DATA-F/A-18 WTT
STRUCTURAL
Device transport method: 3 ton capacity overhead bridge crane at high bay.
Vibration Control. Isolate mechanical room. Resonant frequency = 13 Hz
maximum for light valve platforms.
Special permanent installation/removal equipment: See 3 ton crane above.
MECHANICAL
SPACE NAME
TEMPERATURE
HUMIDITY
SPECIAL
REMARKS
DEGREES(f)
PERCENT
DUCTING
Device/Trainee Area
60-80
40-60
remark 1
2
Instructor/Operator
60-80
40-60
remark 4
Debrief Station
60-80
40-60
Computer Room (CIG)
60-80
40-60
remark 5
Computer Room (digital)
60-80
40-60
remark 5
Mechanical Pump Room
50-90
10-90
3
Maintenance Room
70-80
40-60
Maintenance Storage
70-80
40-60
General Notes:
Refer to WTT Trainer Equipment Summary and architectural for equipment
cooling supply/exhaust ports and equipment and personnel loads. Include heat
Remarks:
1.
Non-motion versions require special ducting by the manufacturer from
trench to inside the dome and cockpit.
2.
24 inch wide x 18 inch deep trench. Slope to drain to sewer or
sump.
3.
Fresh air ventilation
4.
Cool air supply ports direct to underside of console.
5.
Under access floor supply plenum. Provide perforated panels as
required for airflow.
39