MIL-HDBK-1027/4A
Table 2.6 (Continued)
TRAINER FACILITIES DATA-F/A-18 PTT
MECHANICAL
SPACE NAME
TEMPERATURE
HUMIDITY
DEGREES(f)
PERCENT
Device/Trainee Area
50-98.6
80 (max)
Computer Room Area
50-98.6
80 (max)
Maintenance Area
70-80
40-60
ELECTRICAL
SPACE NAME
VOLTS
HZ
AMPS
WIRE PHASE LIGHT ZONE REMARKS
COUNT
LEVEL
Device/Trainee Area
120/208 60
75
4+GND 3
50fc
2
1,2,3
Computer Area
(see TFR)
3
Maintenance Area
120
60
20
2+GND 3
70fc
1
Remarks:
1. 100 ampere service recommended for trainers.
2. Dimming control or fluorescent tube switching recommended.
3. Provide utility outlets at every other cabinet and at each trainee
station for service lighting.
General Notes:
Power Regulation & Filtering:
suppression filters.
Training Devices Connects: Provide 75 ampere master switch circuit breaker.
Device contractor supplies component wiring and conduit from device to
government disconnects or panel.
Grounding: DC power supply ground and digital and analog signal grounds
required. Provide isolated system tied to single common point.
(if required)