UFC 4-171-05
1 January 2005
with change 25 October 2006
APPenDIX F
tOILet ROOM FIXtURe COUnts
F-1
Counts
F-1.1
The minimum fixture count \ for the Training Center Building /2/ should be
based on the tables below for the maximum drill weekend. \ Minimum fixture counts
for other buildings are based on their projected population./2/ Review male/female
personnel ratios with Tenants.
F-1.2
As an alternative method of calculating fixtures, use 40% of the maximum drill
weekend for female toilet fixtures, and 80% for males. Consider the male/female ratio
within the Tenant units when determining ratio of male to female locker, toilet and
shower space.
F-1.3
\ Space column listed in the two tables below is a suggested or targeted
area, if this square foot figure is exceeded, designer must ensure space is below
allowance as set forth in AR 140-483. /2/
F-2
Fixture Count Tables \
F-2.1
Female Toilet Room Fixture Counts
Recommended/
Peak
Water
Total
Suggested
Occupancy
Closets
Lavatories Showers
Fixtures
Space
1 to 15
1
1
1
3
150 SF
16 to 30
2
2
2
6
285 SF
31 to 35
2
2
3
7
325 SF
36 to 45
3
3
3
9
380 SF
46 to 55
3
3
4
10
420 SF
56 to 60
4
3
4
11
450 SF
61 to 75
4
4
5
13
515 SF
76 to 80
4
4
6
14
555 SF
81 to 90
5
4
6
15
585 SF
91 to 105
5
5
7
17
650 SF
106 to 110
5
5
8
18
690 SF
111 to 120
6
5
8
19
690 SF
121 to 125
6
5
9
20
740 SF
126 to 135
6
6
9
21
740 SF
136 to 150
6
6
10
22
740 SF
151 to 165
7
6
11
24
840 SF
166 to 170
7
6
12
25
840 SF
171 to 180
7
7
12
26
840 SF
181 to 190
7
7
13
27
890 SF
191 to 195
8
7
13
28
940 SF
196 to 210
8
7
14
29
940 SF
211 to 215
8
7
15
30
990 SF
216 to 225
8
8
15
31
990 SF
226 to 230
8
8
16
32
990 SF
231 to 240
9
8
16
33
1,040 SF
189