MIL-HDBK-1027/1B
Table 13 (Continued)
19F5 and 19F5A Structures
________________________________________________________________
AGENT USAGE
________________________________________________________________
NO. OF
CLASS
NO. OF
HOSES
AFFF
PKP/
CO2/
WATER
OF
FIRES/
40 mm
WATER
6%
FIRE
FIRE
TIME
FIRE
CLASS
FIRE
L/s
L/s
kg
kg
min
A
160
2
6
2
B
160
1
6
2
1
6
5
1
C
160
5
________________________________________________________________
Notes: 1. The design water demand is: ((6)2 + 6 + 6)2 =
48 L/s.
2.
Portable PKP extinguishers should require 80 CO2
charges per class.
3. No OBA's should be used.
4. Portable extinguishers should be used for fighting
fires with PKP.
________________________________________________________________
TOTAL UTILITIES
________________________________________________________________
CLASS 1 DAY
WEEKLY
Propane
820 700 L
4 103 500 L
Water
379 950 L
1 989 750 L
AFFF Concentrate (100%)
3456 L
17 282 L
PKP
73 kg
363 kg
CO2
363 kg
1816 kg
________________________________________________________________
Notes: 1. The water category includes the water portion of
AFFF (94 percent water, 6 percent AFFF for design).
2. Continuous operation can be assumed for weekly and
monthly consumption.
________________________________________________________________
125