Project Name
Project Number
TEMF
Statement of Work
UFC 4-214-02, 24 Jul 03
Federal, state, and local emission regulations. Oil-fired burners and controls for oil-fired units
firing No. 2 oil shall be atomizing, forced-draft type in conformance with UL 726.
10-8.3
Hot water boilers, dual fuel fired. Boilers shall be gas fired and oil fired. Boilers shall
be designed, constructed and equipped in accordance with the ASME Boiler Pressure Vessel
Code, Section IV, Heating Boilers. Each boiler shall be of the [firetube] [watertube] [cast iron]
type. The boiler capacity shall be based on the ratings shown in HYI-01 or as certified by the
American Boiler Manufacturers Association, or American Gas Association. Boiler shall be
designed to burn gas and oil. Each boiler shall comply with Federal, state, and local emission
regulations. Combination gas and oil-fired units shall conform to UL 296. Burner shall be
provided complete with fuel supply system in conformance with ASME CSD-1 or NFPA 8501.
10-8.4
Steam converter. Exchangers shall operate with steam in shell and low temperature
water in tubes. Shell and tube sides shall be designed for 1035 kPa working pressure and
factory tested at 2070 kPa. Steam, water, condensate, and vacuum and pressure relief valve
connections shall be located in accordance with the manufacturer's standard practice. Tubes
shall be seamless copper or copper alloy, constructed in accordance with ASTM B 75 or ASTM
B 395, ASTM B 395M, suitable for the temperatures and pressures specified.
10-9
CENTRAL COOLING EQUIPMENT. Minimum equipment efficiencies shall be
Energy Star or in accordance with the following minimum efficiencies:
Minimum Efficiencies for Air-Cooled Chillers
Full Load
IPLV
COP (EER)
COP (kW/ton)
527 kW (150 tons) or less
2.8
(9.5)
3.1
(1.12)
greater than 527 kW (150 tons)
2.7
(9.2)
2.9
(1.22)
Air-Cooled (Condenserless):
All Capacities
3.1 (10.6)
3.2
(1.10)
Minimum Efficiencies for Water-Cooled Chillers
Full Load
IPLV
Capacity
COP
(EER)
COP (kW/ton)
281 kW (80 tons) or less
3.9
(13.3)
4.7
(0.75)
greater than 281 kw (80 tons)
or less than or equal to
351 kw (100 tons)
3.9
(13.3)
5.1
(0.70)
greater than 351 kw (100 tons)
or less than or equal to
702 kw (200 tons)
4.7
(16.0)
5.4
(0.65)
SOW-94