TABLE 1
Requirements for Gasoline Dispensing Pumps and Islands
Storage
Number of
Pumps
Number
Air &
Tank
Units
of
Water
Capacities
Supported
Single
Double
Islands
Outlets
gal
outlet
outlet
(under
ground)
Up to 150
1
---
1
2
5,000
151 to 500
2
---
1
2
10,000
501 to 750
1
1
1
2
15,000
751 to 1000
---
2
1
4
20,000
1001 to 1500
---
3
2
4
30,000
1501 to 2000
---
4
2
4
40,000
b.
Air and Water. The diesel fuel dispensing island shall be equipped
with one air outlet and one water outlet, each with automatic retracting
mechanisms. The piping design for the island air and water should incorporate
a shutoff arrangement from the main source of supply, to permit draining the
system when not in use or to prevent freezing during winter months.
9.
EQUIPMENT PARKING AREAS (OPEN STORAGE). A preventive maintenance holding
area and motor pool open storage lot located adjacent to the main
transportation repair facilities shall be provided. Area requirements tor the
open storage lot shall be based on allowing 40 square yards per unit of
equipment for approximately 75 percent of the equipment supported. The 40
square yards per unit takes into account such items as a mixed fleet of
equipment, space requirements for entrance and exit roads, and aisles within
the lot. Parking entrance and exit aisles within the lot should be
approximately 30 feet wide, to permit adequate room for parking or removing
vehicles or equipment. The surface material of the lot will depend upon the
geographic location of the activity.