Cooling:
Inside design conditions:
85 maximum for NICAD Shop
10F temperature difference with
outside temperature for Lead Acid Shop
and Storage
78F minimum for Office
Notes:
1.
Mechanical utility requirements indicated above and on previous
page are for estimating purposes only.
2.
Heat gain from equipment in each shop = 5000 BTU/HR based on a
maximum workload of 8 NICAD and 40 Lead Acid batteries per work
shift.
3.
All mechanical equipment and fixtures shall be specified to
withstand the corrosive atmosphere.
Ventilation:
NICAD Shop
Minimum 1 air change/hr. Exhaust 100%
directly to outdoors.
Lead Acid Shop
Minimum 3 air changes/hr. Exhaust 90%
directly to outdoors. Room air
recirculation is not allowed.
ELECTRICAL
Lighting:
Plan Type A
Plan Type B
Connected Load
8Kw
10Kw
Estimated Demand
5Kw
6Kw
Power: (see note 2. on the next page)
Connected Load
75Kw
75Kw
Estimated Demand
45Kw
45Kw
Total:
Connected Load
83Kw
85Kw
Estimated Demand
50Kw
51Kw
TITLE
BATTERY SHOP
DATE
FACILITY PLATE NO.
SHEET
UTILITY REQUIREMENTS
SEPT84
218-50
7