MIL-HDBK-1191
installation of an IDS system. The site preparation for this system will
include allocation of space in a protected area for a control unit, monitor
station and signal processing equipment as well as remote sensors. Intrusion
detection system locations and sensor types to be provided for are as follows:
Location
Balanced Magnetic
Ultrasonic Motion
Duress Alarms
Switch
Detector
X
X
Inpatient and
outpatient
Pharmacy
X
X
X
Inpatient and
Outpatient
Pharmacy
dispensing
Window(s)
Emergency
X
Department
Pharmacy Vault
X
X
Cashier office
X
X
X
Logistics vault
X
X
Logistics
X
X
warehouse
X
X
Silver recovery
central Collection
point
Mental Health
X
The above table is provided for general guidance.
Specific design shall be in
accordance with the using Service guidance.
A magnetic switch shall be placed on each door or window that
could provide access. The motion detector shall cover the entire area. Video
monitoring and recording will be activated by the intrusion detection and
duress alarms (See paragraph CCTV surveillance). Intrusion Detection system
design will follow the established industry guidelines.
11.18.2
CCTV Surveillance. Provisions will be made for GFGI CCTV
surveillance equipment. Conduits with pull wires, outlet boxes, and
electrical power will be provided for the following suggested locations:
cashier office, cashiers in food service and installation exchange, vaults,
stairwell exits on pediatric and psychiatric nursing units and nursery,
computer room, emergency and acute minor illness waiting and reception areas,
corridors connecting buildings, pharmacy dispensing windows, building
entrances and exists, elevator lobbies, loading docks, parking lots, and
ground floor mechanical rooms. The system will be designed such that a camera
will be activated by an intrusion detection alarm or an attempt at
unauthorized access at a card reader. Monitors will be located in a staffed
location.
11.18.3
Door Access Systems. An electronic door access system will be
provided where required by the using Service. The system will be complete and
will include all monitor and control equipment and equipment to produce cards
to discontinue access authorization for issued cards, maintain and provide a
listing of current authorized access by individual, location, and time. An
interface will be provided between the CCTV system and the Door Access System
11-25