MIL-HDBK-1191
D.3.9
4.13.7,p36
If the answer to previous
question is no, delete this
question. Would an ante room to
an isolation room be allowed to
have two doors in line, provided
the following conditions are met?
a.
The approach
requirements or
maneuvering clearances
of each door
considered independent
of the other door
comply with Figure 25.
b.
There is a clear turn-
around space that
complies with Figure 3
in both the ante-room
and the isolation
room.
See Figure D-4.
D.3.10
4.13.7,p36
If two doors in series are
located in walls perpendicular to
each other, is a minimum clear
distance of 48 inches required?
See example plans in Figure D-5.
Yes.
D.3.11
4.16.2 &
There is a conflict between the
4.16.4,p38
36" grab bar dimension and the
36" minimum dimension for
lavatory placement. Is a smaller
grab bar dimension permitted?
No. The drawings in Fig. 28
appear inconsistent with the
technical provisions. However,
nowhere in the text is a shorter
grab bar deemed acceptable.
Since space must be allowed to
accommodate the returns and
escutcheons of the 36" grab bar,
we recommend a minimum space of
39" to the edge of the lav. One
must recognize also that this
allowable arrangement does not
permit a side transfer, only a
diagonal transfer to the water
closet from a wheelchair.
D.3.12
4.16.6,p38
What is the maximum height
allowed for a toilet paper
dispenser?
Not addressed, other than the 19"
Apdx D-5