MIL-HDBK-1191
not to require full accessibility
with a turnaround space in the
following spaces:
flammable storage (50)
equipment Storage (50)
barium prep (70)
soiled linen (60)
clean utility rooms (60)
sterile storage (60)
lab incubation room (70)
forms
storage (50)
anesthesia gas storage (50)
baggage storage (40)
trash collection (60)
acid
storage (40)
plaster prep storage (50)
gas
storage (40)
chemical mix/storage (30)
parts storage (80)
work rooms - nursery (50)
vaults (40)
music/paging controls (50)
scrub areas (50)
radium sealed source rm (60)
injection room (50)
(Note: The numbers in parenthesis
indicate the net square footage
that has been traditionally
assigned to these functions.)
Depends on actual use and whether
these spaces are restricted to
use by able-bodied military
personnel only. It is
recommended that accessibility be
provided wherever possible
because the use of the room or
space may change over time.
D.3.34
Projection rooms are
approximately 200 square feet and
may be one level above the
auditorium floor. Is it the
intent of this standard to
require
an elevator for
accessibility to this space, if
this is the only space served?
Must be reviewed individually.
If opportunity exists,
accessibility should be provided.
If not, perhaps the situation
warrants a waiver application.
D.3.35
Computer rooms in medical
facilities may be sized as small
as 100 to 200 square feet. Is it
Apdx D-11