LIGHTING
Table
4-7
Lighting
Standards
for
Generic
Spaces
Generic
Space
Ft. Candles on Task
1. - Entry, incl. s e c o n d a r y
entries:
( e n t r a n c e foyer)
30
coat room ( locker rooms)
20
t e l e p h o n e room (telephone equip. room)
20
2 - Dining (dining areas)
cashier station
50
(intimate type, light environment)
10
( i n t i m a t e t y p e , s u b d u e d environment)
3
(for cleaning)
20
( l e i s u r e t y p e , light
environment)
30
( l e i s u r e type subdued environment)
15
(quick service type, bright surroundings)
100
( q u i c k s e r v i c e t y p e , n o r m a l surroundings)
50
( f o o d d i s p l a y s , t w i c e normal but not less
than:)
50
maitre'd station
NA
waitress station
NA
serving center
NA
3 - Bar
alI
sub-spaces
NA
4 - Kitchen
alI
sub-spaces
(kitchen,
commercial)
70
5 - Ballroom/Multi-Use
( d a n c e halls)
5
(auditoriums,
assembly)
15
(auditoriums,
exhibition)
30
(auditoriums, s o c i a l a c t i v i t i e s )
5
d r e s s i n g rooms (locker rooms)
20
6 - Party
alI
types
- See
Dining,
Ballroom
&
Recreation
7 - Recreation, quiet
r e a d i n g (lounge and reading rooms)
30
l o u n g e (lounge and reading rooms)
30
T . V . room
NA
8 - Recreation, noisy
games (table
games)
30
pool table
50