SMALL OFFICERS CLUB
7-3.8 STEP M - UTILITY & THERMAL LOADS
7-3.8.1
Building
data
1,273
s.f.
A.
Gross
floor
area
B.
Max. population at one time
52
C.
100
Max. meals served/day
7-3.8.2
Utility
loads
Electrical :
Light and power
49 kva
A.
32 gpm
B.
Water:
Max.
flow
rate,
cold
water
32 gpm
Max.
flow
rate,
hot
water
T o t a l f l o w per day
1 , 0 0 0 gal.
1 , 0 0 0 gal.
Total gall
ons per day
C.
Sewage:
ing
loads
7-3.8.3
and
cool
40 MBTU/hr.
Load
A.
5 . 7 5 tons
B.
Air
conditioning:
Tons
of
refrigeration
7-3.8.4
Design
assumptions
A l l policy and design criteria per DOD 4270.1-M.
A.
E s t i m a t e s are for plans shown.
B.
Heat
load
in
kitchen
not
included
in
heat
gain
calculations.
C.
D.
Single glazing, standard glass.
E.
20%
outside
air
assumed
for
ventilation
40 BTU/hr./ft.
F.
A s s u m e d perimeter heat loss:
G.
Sewage demand based on 10 gpd per person, max. occupancy.
H.
Lighting
load
assumed
2.5
watts/s.f.
7-20