MEDIUM NCO CLUB
7-7.13 STEP M - UTILITY & THERMAL LOADS
7-7.13.1
Building data
A.
Gross
floor
area
17,609
s.f.
B.
Max. population at one time
486
C.
Max.
meals
served/day
635
7-7.13.2
Utility loads
A.
Electrical:
L ight and power
690 kva
B.
Water:
Max. f low rate, c o l d
60 gpm
water
M a x . f l o w rate, hot water
60 gpm
T o t a l flow per day
6,350
gal.
C.
Sewage:
Total
gallons
per
day
6,350
gal.
7-7.13.3
and
cooling
loads
A.
Load
698 MBTU/hr.
B.
Air
conditioning:
Tons
of
refrigeration
6 1 tons
7 - 7 . 1 3 . 4 Design assumptions
A l l policy and design criteria per DOD 4270.1-M.
A.
Estimates are for plans shown.
B.
C.
Heat
load
in
kitchen
not
included
in
heat
gain
calculations.
D.
Mechanical
room
ventilated
only.
E.
Single glazing, standard glass.
F.
20%
outside
air
assumed
for
ventilation.
G.
Assumed perimeter heat loss:
40 BTU/hr./ft.
H.
Sewage demand based on 10 gpd per person, max. occupancy.
Lighting
load
I.
assumed
2.5
watts/s.f.
7-70