CEMP-E
TI 810-32
10 January 2002
PIPE
PIPE
INSULATION
INSULATION
SEE NOTE 2
SEE NOTE 2
TYP.
1/4
SEE NOTE 3
*
*
1 1/2 "
1 1/2 "
SEE NOTE 1
*
8"
S-1
S-2
PIPE 2" THRU 10"
PIPE 12" THRU 24"
HEAT INSULATED PIPING
(100^F - 750^F)
SHOES FOR CARBON STEEL PIPE
MATERIAL
TYPE
STEEL ASTM
SIZE
CARBON A-36
ST 6 X 15.9 X 16" LONG
S-1
1 PLATE
8" X 16" X 1/4 " THK. (HORIZ.)
S-2
CARBON A-36
2 PLATES
6" X 16" X 1/4 " THK. (VERT.)
NOTES:
1. WELD THICKNESS SHALL BE SAME AS PIPE SHOE OR PIPE WALL
THICKNESS, WHICHEVER IS THINNEST.
2. WHERE INSULATION IS GREATER THAN SHOE HEIGHT, CUT AWAY
INSULATION PARTIALLY WHERE IT INTERFERES WITH PIPE
SHOES AND SUPPORTS.
3. SEE TABLE 4-1 FOR CHANNEL SUPPORT SCHEDULE.
FREE PIPE SUPPORT
FS
NO SCALE
Figure 4-1. Free Pipe Support Detail.
4-4