(4) Collector temperature sensor mounting details. Detail showing
mounting of the collector array temperature sensor should be provided. The sensor
should show either mounting in the upper manifold piping between two collectors or
should show mounting by the manufacturer directly to the absorber plate.
(5) Building piping penetrations. Design of piping penetration is weather
tight and will withstand temperature expansion variations from 350 degrees F (177
degrees C) to the design low temperature of the project location.
(6) Pipe support. Pipe support design allows for temperature expansion
variations from 350 degrees F (177 degrees C) to the design low temperature of the
project location.