3.6.1
Bulk Air Eliminators. Use flange-connected, steel
bodied bulk air eliminator of the desired pressure and flow
rating for the applicable service requirement. Include an
automatic air release head and interlock the equipment with a
float or solenoid-operated hydraulically operated diaphragm
control valve. Provide discharge piping to the product
recovery system or other safe means of containment.
3.6.2
Meters - Positive Displacement. Require flange-
the desired pressure and flow rating for the applicable
service requirements. Ensure meter has temperature-
compensation (if custody transfer), adjustable calibration,
register and pre-set capabilities. Ensure meter accessories
are compatible with either the mechanical or electronic
support equipment selected. Provide an accuracy of plus or
minus 0.5 percent when used for custody transfer. Consult the
appropriate Service Headquarters for requirements for the
meter to communicate to a remote location or equipment.
Consider the use of a card-operated or key-operated data
acquisition system. Refer to "Card and Key Locks" under
"Controls" paragraph of this section.
3.6.3
Meters - Turbine. Use flange-connected, steel
bodied turbine meters of the desired pressure and flow rating
for the applicable service requirement. Ensure meter has
temperature-compensation and adjustable calibration. Provide
an accuracy of plus or minus 0.5 percent when used for custody
transfer. Ensure all supporting equipment for meter is
compatible with the turbine meter selected. Consult the
appropriate Service Headquarters for requirements for the
meter to communicate to a remote location or equipment.
Consider the use of a card-operated or key-operated data
acquisition system. Refer to "Card and Key Locks" under
"Controls" paragraph of this section.
3.6.4
Meters - Orifice. Use this type of meter only where
custody transfer or accounting/inventory control is not
required. Provide with flange connections.
3.6.5
Pressure or Pressure/Vacuum Gauges. Use liquid-
filled gauges of range and dial size, as necessary, but not
less than 0 to 160 psig (0 to 1100 kPa) pressure range and
4-inch (100 mm) diameter dial. Gauges to be of all stainless
steel construction, with black graduations on a white face.