UFC 3-460-03
21 JANUARY 2003
Electrical components
10.3.20
Quarterly
Hydrant adapters
10.3.21
Semi-annually
Auto tank gauge
10.3.22
Annually
Strainer
10.3.23
As required
Piping
Pressure test
10.3.6.1
Annually
Hydrostatic test
10.3.6.2
Every 5 years
Exposed piping
10.3.6.3
Corrosion control
10.3.6.3.1
Semi-annually
Identification
10.3.6.3.2
Quarterly
Pumps
General maintenance
10.3.7.1
Quarterly
Lubrication
10.3.7.2
Quarterly or per manufacturer
Product recovery
10.3.7.3
Quarterly
Storage Tanks
Vacuum/pressure vent
10.3.4
Semi-annually
Dikes
10.3.5
Annually
Aboveground
10.3.3.1
Visual inspection
10.3.3.1.1
Monthly
API 653
10.3.3.1.2
Every 10 years
Floating roof/pan
10.3.3.2
Seals and pan
10.3.3.2.1
Monthly
Roof drain
10.3.3.2.2
Monthly
Roof drain (antifreeze)
10.3.3.2.4
As required
Cleaning/inspection
10.3.3.3
Without F/S and coating
10.3.3.3.1
Every 4 years
With F/S or coating
10.3.3.3.2
Every 6 years
With F/S and coating
10.3.3.3.3
Every 8 years
10.3.1. System Areas. Large grass-covered areas around fuel systems will be mowed by BCE
personnel or by service contract. Consult the Maintenance Engineering shop for questions
concerning performance of this task by contract.
10.3.2. Hoses.
104