UFC 3-535-01
17 November 2005
Figure 3-10. Light Plane Elevation Limits
420M
360M
(1400FT)
(1200FT)
APPROACH LIGHTS NOT TO BE
MOUNTED ABOVE THIS LINE
16M
(52FT)
+2.0% MAX.
+2.0% MAX.
MAX.
RUNWAY
8M (28FT) MAX.
LEVEL
6M (21FT) MAX.
15M
(51FT)
-2.5% MAX.
-1.0% MAX.
MAX.
THRESHOLD
APPROACH LIGHTS NOT TO BE
MOUNTED BELOW THIS LINE
NOTE: THE BOUNDARIES OF THE LIGHT PLANES ARE THE RUNWAY THRESHOLD, 60M (200FT)
AHEAD OF THE END LIGHT STATION, AND 60M (200FT) EACH SIDE OF CENTERLINE.
3-5.5.1.3
Every effort must be made to remove or relocate objects which penetrate
the light plane. For objects which cannot be moved, the height must keep to a minimum
and must be located as far from the threshold as possible.
3-5.5.1.4
The major command has waiver authority to adjust the slope of the light
can not be removed or lowered..
3-5.6
Tolerance
The tolerances for positioning steady burning MALSR lights are as follows:
3-5.6.1
Lateral tolerance of a bar is 0.15 meters (6 inches).
3-5.6.2
Distance between individual light centers in a barrette is 0.05 meters (2
inches).
3-5.6.3
Height for light centers up to 1.8 meters (6 feet) is 0.05 meters (2 inches).
3-5.6.4
Height for light centers over 12 meters (40 feet) is 0.15 meters (6 inches).
3-5.6.5
Tolerance for vertical aiming of light units is 1.0 degree.
3-5.6.6
Tolerance for horizontal aiming of light unit is 5 degrees.
3-5.6.7
Longitudinal deviation for light bars or single SFL from a designated
station is 6 meters (20 feet), except light stations may be displaced 30 meters (100 feet)
to avoid omitting a light station where obstructions cannot be removed or cleared by
acceptable clearance planes. Where a light station must be located more than 6 meters
34