Table 14-7. Checklist for Underground Cable and Duct (Cont.)
____ 5. Are cable racks and manhole/handhole frame and covers properly grounded?
____ 6. Do ducts terminating in manholes and handholes have end bells, and is duct
penetration properly grouted, plugged or sealed?
____ 7. Has backfilling and compaction been properly done (no trench settlement), and are
disturbed areas properly restored?
____ 8. Are cable or duct markers installed at each change of direction, every 200 feet along
straight run with no access structure, and at ends of all duct that are not terminated
at handholes or manholes?
____ 9. Are cable and duct markers correctly and neatly inscribed?
____ 10. Is sufficient cable slack provided at each primary connector termination?
____ 11. Does the cable insulation meet the minimum resistance requirements?