UFC 3-580-10
14 July 2004
Including changes 12 April 2005
Intermediate Cross Connect - With Cooling Equipment
CABINET
VOLT
EQUIPMENT AMPS SITE COOLING AMPS
FEEDER AMPS
TPP FEEDER
*
COOLING
CABINET
SEAT CNTS
(VOLT/Phase) Phase A
Phase B
Phase A
Phase B
Phase A
Phase B
BK AMP/POLE
Wire Size
Heat to Room
(Btu/hr)
CIDF37
<12
120/208/1 PH.
4
0
0
4
4
4
30/2
3#10, #10G, 3/4"C
1,420
CIDF38
<36
120/208/1 PH.
10
21
0
4
10
25
30/2
3#10, #10G, 3/4"C
5,626
CIDF39
<18
120/208/1 PH.
20
21
10
10
30
31
40/2
3#8, #10G, 3/4"C
7,759
DBASEX1
N/A
120/208/1 PH.
13
12
10
10
23
22
40/2
3#8, #10G, 3/4"C
9,160
DBASEX2
N/A
120/208/1 PH.
7
5
0
4
7
9
30/2
3#10, #10G, 3/4"C
4,478
DIDF15
<192
120/208/1 PH.
7
7
0
3
7
10
30/2
3#10, #10G, 3/4"C
3,728
DIDF20
< 72
120/208/1 PH.
6
10
0
4
6
14
40/2
3#8, #10G, 3/4"C
4,979
DIDF21
<24
120/208/1 PH.
12
8
4
0
16
8
40/2
3#8, #10G, 3/4"C
6,283
DIDF22
<24
120/208/1 PH.
4
5
4
0
8
5
40/2
3#8, #10G, 3/4"C
3,640
DIDF26
<192
120/208/1 PH.
7
7
10
10
17
17
30/2
3#10, #10G, 3/4"C
5,425
DIDF28
<96
120/208/1 PH.
7
7
10
10
17
17
30/2
3#10, #10G, 3/4"C
5,425
DIDF30
<72
120/208/1 PH.
17
17
20
20
37
37
60/2
3#6, #10G, 3/4"C
12,488
DIDF32
<96
120/208/1 PH.
15
15
20
20
35
35
60/2
3#6, #10G, 3/4"C
11,075
DIDF34
<144
120/208/1 PH.
16
9
10
10
26
19
40/2
3#8, #10G, 3/4"C
8,815
DIDF36
<96
120/208/1 PH.
10
7
10
10
20
17
40/2
3#8, #10G, 3/4"C
7,401
DIDF45
<24
120/208/1 PH.
7
7
0
4
7
11
30/2
3#10, #10G, 3/4"C
5,227
DIDF49
<48
120/208/1 PH.
1
1
0
4
1
5
30/2
3#10, #10G, 3/4"C
5,227
DIDF52
<24
120/208/1 PH.
10
5
0
4
10
9
30/2
3#10, #10G, 3/4"C
5,619
DIDF53
<96
120/208/1 PH.
12
22
20
20
32
42
60/2
3#6, #10G, 3/4"C
9,071
HIDF8
<24
120/208/1 PH.
5
5
0
4
5
9
30/2
3#10, #10G, 3/4"C
3,754
HIDF13
< 48
120/208/1 PH.
5
10
0
4
5
14
30/2
3#10, #10G, 3/4"C
4,277
HIDF40
< 18
120/208/1 PH.
5
5
0
3
5
9
30/2
3#10, #10G, 3/4"C
3,920
HIDF46
<24
120/208/1 PH.
7
7
0
4
7
11
30/2
3#10, #10G, 3/4"C
5,227
67