UFC 3-600-01
26 September 2006
A minimum of 7.6 m (25 ft) from any buildings of Type I or Type II
construction.
6-20.4
Bulk Tank Vehicle Parking.
Design parking for bulk tank vehicles servicing fixed tanks that meet the
separation requirements of NFPA 55, for the fixed bulk tank.
Exception: As modified in paragraph 6-20.3.
6-20.5
LOX Storage for Propellant Applications.
Use liquid oxygen storage for propellant applications that comply with 29 CFR
Exception: As modified in paragraph 6-20.3.
6-21
DEPARTMENT OF DEFENSE DEPENDENT SCHOOLS
(DODDS).
DoDDS facilities must comply with paragraph 4-2.2 and with the educational
occupancy in NFPA 101.
6-22
VEHICLE PARKING, STORAGE, MAINTENANCE, AND REPAIR
FACILITIES.
Design facilities utilized for the parking, storage, maintenance, and repair of
general and special purpose motor vehicles to comply with NFPA 88A, Parking
Structures and/or NFPA 30A, Code for Motor Fuel Dispensing Facilities and
Repair Garages.
6-22.1
Vehicle Parking.
Protect enclosed buildings used for vehicle parking and storage of 10 or more
vehicles with an automatic sprinkler system.
6-22.2
Overhaul and Repair Shops.
Facilities falling within this category are those in which major overhaul and
repairs are made to various types of equipment or their component parts.
Disassembly and testing may also be performed in such facilities, which include
aircraft shops, automotive garages and repair shops, and ship repair shops.
6-22.2.1
Requirements.
Design automotive garages to conform to NFPA30A. Design ship repair facilities
to conform to NFPA 303 and NFPA 312. Design major aircraft overhaul and
repair shops to conform to paragraph 6-16.
70