UFC 3-600-01
26 September 2006
6-22.3
Refueler Vehicle Facilities.
Facilities that are covered and enclosed on at least three sides and that are used
for the parking, storage, maintenance, and repair of aircraft refueler vehicles
must:
6-22.3.1
Be protected by an automatic sprinkler system or a closed-head
foam-water AFFF sprinkler system, and
6-22.3.2
Utilize Class I Division 2 electrical equipment and wiring as defined
by NFPA 70.
6-23
PESTICIDE STORAGE AND HANDLING FACILITIES.
Locate facilities or operations involving the storage, mixing, or handling of non-
flammable pesticides a minimum of 30.5 m (100 ft) from the nearest building or
occupied structure.
Exception 1: Facilities of Type I construction as defined by the IBC, may be
located less than 30.5 m (100 ft) from the nearest building or occupied structure,
but not less than 9.1 m (30 ft) in any case.
Exception 2: Facilities protected by an automatic sprinkler system may be
located less than 30.5 m (100 ft) from the nearest building or occupied structure,
but not less than 9.1 m (30 ft) in any case.
Exception 3: Existing facilities involving the storage, mixing, or handling of non-
flammable pesticides are permitted in a building when all the following are
provided:
The building is completely protected, including the pesticide area,
by an automatic sprinkler system.
The pesticide area is separated by not less than one-hour fire rated
construction from the remainder of the building.
Duct work that penetrates fire rated partitions and wall assemblies
is provided with smoke and fire dampers.
6-24
WINDOWLESS (LIMITED ACCESS) STRUCTURES.
Windowless (limited access) structures are defined in and must conform to the
requirements in NFPA 101. Provide windowless (limited access) structures three
stories or more in height with a manually activated smoke exhaust system.
6-24.1
Sprinkler Protection.
71