UFC 3-600-01
26 September 2006
2044 m2 (22,000 ft2)
3
6. Firefighting access
51.8 m (170 ft)
2
Total Weighing Value
12
Per Table C-1: 4260 L/m (1125 gpm ) for 90 minutes
(2) Example 2 - Welding Shop (Ordinary Group 1)
Factors
Values
1. Fire Department response
Off-site (within 3.2 km (2 miles))
2
2. Type of construction
Type II
3
3. Number of Stories
Single story
1
4. Separation Distance
6.1 m (20 ft)
4
5. Building Floor Area
2044 m2 (22,000 ft2)
3
6. Firefighting access
76.2 m (250 ft)
4
Total Weighing Value
17
Per Table C-1: 7570 L/m (2000 gpm) for 150 minutes
(1) Example 3 - Barracks (Light Hazard)
Factors
Values
1. Fire Department response
Off-site (more than 4.8 km (3 miles))
3
106