UFC 4-021-02NF
27 September 2006
change 1, 23 October 2006
Figure 7-2. Example RDC
7-1.3
Small facilities not located on a DoD installation such as Reserve Centers,
medical clinics, or pharmacies may be connected to a Central Station or Police Station.
7-2
SPACE
7-2.1
Space programming for a Dispatch Center should consider the following:
7-2.1.1
Equipment wall space
7-2.1.2 A minimum of three-foot clearance in front ( and rear if used for service) of all
electrical cabinets and enclosures (NFPA 70 requirement).
7-2.1.3
Counter space for consoles
7-2.1.4
Personnel space for each operator
7-2.1.5
Space for UPS equipment
7-2.1.6
Access requirements for maintenance or repair.
7-2.1.7
Conduit space requirements for future system wiring or enhancements.
7-2.1.8
Future growth or expansion space
108