MIL-HDBK-1024/1
b)
Parking of POV's within 15 feet of any building is prohibited.
c) Parked vehicles within either the 20-foot minimum outside
security zone or the 30-foot minimum inside security zone associated with
restricted area security fencing is prohibited.
2.2.3.2
Access for Fire Department Apparatus. Consult local authorities
having jurisdiction for criteria regarding access to the area and clearance
around the buildings for fire apparatus maneuvering. The equipment expected
to respond to an emergency will control these decisions. See National Fire
Protection Association (NFPA) 1141, Fire Protection in Planned Building
Groups.
2.2.4
Site Drainage. Provide drainage design in accordance with
are inappropriate at some sites. Establish requirements for use of metallic
pipe and reinforced concrete pipe early in facility planning. Consider
drainage swales with minimal velocities to avoid damage of ground planes. Do
not use storm drain pipes through an antenna ground plane. Refer to
MIL-HDBK-1012/1.
2.2.5
Protection of Fixed Objects. Provide barriers to protect electrical
transformers, generators, fuel tanks, fire hydrants, etc., from damage due to
2.2.6
Airfield Safety. Consider safety clearances when siting facilities
in or near aviation operational areas. Refer to NAVFAC P-80.3, Facility
Planning Factor Criteria for Navy and Marine Corps Shore Installations,
Appendix E: Airfield Safety Clearances and Title 14, CFR Part 77, Objects
Affecting Navigable Airspace. Objects located within runway clear zones shall
be fabricated for low impact resistance in accordance with FAA Engineering
Resistance for Microwave Landing System Structures (MLS/LIRS). Objects
penetrating the airspace surfaces described in NAVFAC P-80.3 and Title 14, CFR
Part 77 require a waiver of clearance criteria. The point of contact for
waiver of Navy criteria is NAVAIRSYSCOM, Code AIR-09Y1. The point of contact
for waiver of FAA criteria is the Chief, Air Traffic Division of the FAA
Regional Office having jurisdiction over the area within which the
construction will be located. Provide obstruction marking or lighting for
facilities located in or near aviation operational areas in accordance with
FAA Advisory Circular AC 70/7460, Obstruction Marking and Lighting.
Objects Located on Airfield. Location of any objects within
2.2.6.1
airfield clear zones and/or airspace surfaces will be made by NISE-EAST with
NAVAIRSYSCOM concurrence.
2.2.6.2
Objects in Violation of Airfield Safety Criteria. Objects that must
be located in violation of NAVFAC P-80 and NAVFAC P-80.3 criteria shall be
located to result in the minimum violation possible compatible with the
6