MIL-HDBK-1024/1
+)))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))))),
*
*
Joint Control Facility *
*
*
*
* Plumbing Requirements (GPM):
*
Medium
High
*
*
Water;
Density
Density
*
*
*
*
Cold
74
74
*
*
Hot
*
*
Recovery Rate (100 Degs. Rise)
100
100
*
*
Storage (Gal.)
160
160
*
*
Fire Protection Requirements
*
*
Not Included
*
*
* Heating Requirements (BTU/HR x 1000):
*
*
*
(Inside Design Temperature = 72 Degs. F)
*
*
Outside Design Temperature
-5 Degs. F
490
600
*
*
+5 Degs. F
430
530
*
*
-15 Degs. F
380
460
*
*
-25 Degs. F
295
360
*
*
*
*
*
Based on 91 Degs. D.B.
76 Degs. W.B. Outside Design Conditions;
*
*
Cooling Load
1620
2140
*
*
*
*
Heat rejected to conditioned spaces by energized test.
*
*
Equipment & parts under repair not included.
*
*
* Electrical Requirements (KVA):
*
*
*
Lights;
*
*
Connected Load
90
90
*
*
Estimated Demand
63
63
*
*
*
*
Power;
*
*
Connected Load
514
610
*
*
Estimated Demand
360
427
*
*
*
*
*
*
Connected Load
377
784
*
*
Estimated Demand
264
550
*
*
*
*
Total;
*
*
Connected Load
981
1484
*
*
Estimated Demand
687
1040
*
*
400
600
*
*
* Areas (SF):
*
*
*
Gross area including mechanical
*
*
equipment room
33,970
39,500
*
*
*
*
*
*
/))))))))))))))))))))))))))))))))))0)))))))))0))))))))))))))))))))))0))))))))1
* TITLE
* DATE
*
* SHEET *
FACILITY PLATE
*
Joint Control Facility *
*
*
*
*
* 11/92 *
* 7 OF 7 *
Design Notes
133-74
.))))))))))))))))))))))))))))))))))2)))))))))2))))))))))))))))))))))2))))))))-
109