MIL-HDBK-1027/1B
a)
Classrooms and offices
b)
Locker rooms and restrooms
c)
Storage rooms
d)
Staging and training areas
e)
Quarterdeck or 24-hour duty station
f)
Main corridors and vestibules
g)
Mechanical and fan rooms
h)
Propane storage areas
3.12.6.3 Propane Warning Signs. Provide separate propane
warning signs at the following locations:
a)
Front entrance
b)
Loading dock
c)
Quarterdeck or 24-hour duty station
d)
Instructor and operator station
e)
Propane storage area
Warning signs should be the backlighted type and should flash
when there is an alarm condition. Propane warning signs should
state "DANGER - PROPANE ALERT."
3.12.7
Manual Pull Stations. Provide separate manual pull
stations which actuate an alarm condition at the following
locations:
a)
Outside propane tank storage area
b)
Mechanical rooms
3.12.8
Auxiliary Control Stations. Provide auxiliary control
stations which consist of manual pull stations. Auxiliary
79