MIL-HDBK-1027/1B
control stations should be capable of deenergizing the audible
alarms. Provide auxiliary control stations at the following
locations:
a)
Instructor and operator station
b)
Quarterdeck or 24-hour duty station
3.12.9
Intercom System.
Provide an intercom system to
include the following:
a) Audible alarms should override the intercom system
until the alarms have been secured. When audible alarms have
been secured, the intercom system should be operable. Intercoms
should not be provided in fireplace compartments, crawl space,
and burner rooms.
b) The intercom system should have public
announcement capability with speakers located in all rooms of
the facility, except as noted above.
3.13
19F1A and 19F1B Structures
3.13.1
General. The 19F1A and 19F1B structures should be
used to train in the Advanced Shipboard Firefighting Team
Evaluation Course, J-425-0424. The structure is designed to
train an 0424 class of 30 students and can train two classes or
60 students each week operating a single shift.
3.13.2
structures are in Appendix B.
3.13.2.1 Layout. The 19F1A and 19F1B structures contain eight
training quadrants on two floors accessible by a centrally
located corridor. Staging should be done on the upper level.
The structure, including the corridor, should be divided in half
by a smoke tight wall allowing for separate and independent
training to proceed simultaneously. To better control the
products of combustion, the second floor crawl space floor
should also be smoke tight. Corridor walls and the escape trunk
enclosure should be continuous from the crawl space floor to the
concrete ceiling over the training compartment. Provide
80