MIL-HDBK-1027/1B
two 2-day 0413 classes of 60 students and one 1-day 0414 class
of 30 students a week. Approximately 6000 students can be
trained a year.
3.16.2
structures are in Appendix E.
Table 11
19F3A and 19F3C Ventilation Air
________________________________________________________________
PROPANE
VENTILATION
DEMAND
AIR OUT AT
COMPARTMENT
L/s
316 Degrees C L/s
________________________________________________________________
1
83
14 774
2
83
14 774
3
5
2171
4
9
4342
5
9
4342
6
9
4342
7
5
2171
8
5
2171
Pit
186
56 640
________________________________________________________________
Note:
Fan static pressure should be determined by bringing
16 degrees C air through the louvers and exhausting
316 degrees C through the exhaust system.
________________________________________________________________
3.16.2.1 Layout. The 19F4 and 19F4A structures are designed to
simulate aircraft fires onboard ship. The structure consists of
an open training deck measuring 34 138 mm by 20 117 mm with one
fireplace. The training deck should be constructed of concrete.
The fireplace should be 15 850 mm by 10 973 mm centered leaving
two 9144 mm wide and two 4572 mm wide areas for staging. These
4572 mm wide areas are acceptable even though the fire should be
fought from any one of the four sides. There should be no more
than three to five trainees on a 40 mm hose and 7 to 10 trainees
on a 65 mm hose. The remainder of the class should observe the
exercise. The perimeter of the fireplace should be lined with
110