MIL-HDBK-1191
TABLE 7-2
DESIGN ENERGY TARGETS (DET) FOR DoD MEDICAL AND DENTAL (1)
TREATMENT FACILITIES - MJ/m2/yr (1000 BTU/ft2/yr))
BUILDING
REGION
REGION
REGION
REGION
REGION
REGION
REGION
CATEGORY CODE
1
2
3
4
5
6
7
(2)
CDD (3):
< 1110
< 1110 < 1110 < 1110
< 1110 > 1110 > 1110
:
<(2000)
<(2000) <(2000) <(2000)
<(2000) >(2000) >(2000)
:
HDD (3):
> 3885
3055-
2220-
1110-
0-
0-
2000-
:
3885
3055
2220
1110
1110
1110
:
>(7000)
(5500-
(4000-
(2000-
(
0-
(
0-
(2000-
:
7000)
5500)
4000)
2000)
2000)
4000)
510 Hospital
1530
1530
1190
1140
1140
11909
1250
Buildings (4)
(135)
(135)
(105)
(100)
(100)
(105)
(110)
530 Labora-
510
510
400
400
400
400
400
tories
(5)
(45)
(45)
(35)
(35)
(35)
(35)
(35)
540 Dental
740
740
620
570
450
510
680
Clinics
(5)
(65)
(65)
(55)
(50)
(40)
(45)
(60)
550 Dispen-
740
740
570
510
400
450
620
saries
(5)
(65)
(65)
(50)
(45)
(35)
(40)
(55)
TABLE 7-2 NOTES:
(1) Energy consumed within 1.5 m (5 ft) line, based on Dept. of
Energy building categories and weather zones. The DET for a building within
which more than one category is found shall be the sum of the area-factored
DET's for the given categories. A minimum 10% of the total area shall be
dedicated to the given category to be factored into the DET.
(2) Degree-Day value from the joint service Manual TM 5-785,
NAVFAC P-89 and AFM 88-29 Engineering Weather Data shall be used.
(3)
Cooling Degree Days - CDD; Heating Degree Days - HDD
(4)
24 hours/day, 7 days/week.
(5)
10 hours/day, 5 days/week.
7-7