MIL-HDBK-1191
FACILITY TYPE
PASSENGER CARS
COMBINE USE AND
DEDICATED MATERIALS
PATIENT SERVICE CARS
CARS (MANUAL SYSTEMS)
WAREHOUSE
LESS THAN 50 SECONDS
NOT APPLICABLE
LESS THAN 60 SECONDS
TROOP AID STATION
LESS THAN 45 SECONDS
LESS THAN 50 SECONDS
LESS THAN 60 SECONDS
MEDICAL AND OR DENTAL CLINIC
LESS THAN 40 SECONDS
LESS THAN 45 SECONDS
LESS THAN 55 SECONDS
RESEARCH LABS
LESS THAN 45 SECONDS
LESS THAN 50 SECONDS
LESS THAN 55 SECONDS
HOSPITALS
LESS THAN 35 SECONDS
LESS THAN 40 SECONDS
LESS THAN 50 SECONDS
AVERAGE INTERVAL PERFORMANCE STANDARDS
5 MINUTES OF HEAVY 2-WAY TRAFFIC
TYPICAL FACILITY
FIGURE 17.2
PERCENT OF ELEVATOR POPULATION HANDLED
FACILITY TYPE
MINIMUM ACCEPTABLE, SEE NOTES 1 AND 2
WAREHOUSES, STAND ALONE
11%
TROOP AID STATION, STAND ALONE
12%
MEDICAL AND OR DENTAL CLINIC, STAND ALONE
13%
RESEARCH LAB BUILDINGS, STAND ALONE
13%
HOSPITALS, MEDICAL CENTERS
15%
NOTES FOR FIGURE 17.3:
1. WHERE COMBINED/INTEGRATED WITH ANOTHER FACILITY TYPE, THE HIGHER FACILITY CAPACITY SHALL BE MET.
2. WHERE MORE THAN ONE ELEVATOR GROUP EXISTS, A 10% (MINIMUM) MIGRATION FACTOR SHOULD BE INCLUDED
FOR EACH GROUP.
PASSENGER HANDLING CAPACITY
5 MINUTES OF HEAVY 2-WAY TRAFFIC
TYPICAL FACILITY
FIGURE 17.3
17-20