||content||
\ The Activity preparing the RFP shall address the adequacy of the existing water supply to meet the
demands of the fire protection system required. The Activity preparing the RFP shall perform or
witness the required water flow testing and verify that test results are accurate. Flow testing shall be
conducted at or near the point of connection to the existing water main. Accepting historical water
supply information without verification is not acceptable. The Activity preparing the RFP shall perform
a preliminary hydraulic analysis to determine if the existing water supply is adequate to meet the
demand, or if a fire pump and water storage tank is needed. Information shown below must be
completed by the RFP preparing Activity. /1/
A