Design Guide: Recreation Centers Individual Space Criteria January 1976
the use of broken up wall panels or bulletin
boards.
Perimeter built-in benches should also be
considered for seating as well as for display
purposes.
Provide securable storage for tables, chairs and
supplies.
(6) Technical Requirements
Figure 4-15 Open Multipurpose Space Alternative Use
70 ftc, work surfaces; 30
Level
Plans
ftc, display areas
fluorescent task; light track
Type
for displays
Walls
tackable surface, vinyl or
local switch with dimmer
Control
cork covered
sheet viny I or resin epoxy
Floors
(b) Power
exposed structure
Ceiling
1 every 12' of partition
Outlets
(d) Colors
clock outlet mtd 2' below
Special
ceiling
off -white
Walls
primary accent colors and
Accents
(c) Plumbing
charcoal
Janitor's sink
(d) H V A C
Summer
78DB; 65WB; RH 50%
Winter
68-72
Air changes 6 per hour
P/A
1 station
1 speaker station; 3 head-
Sound
phone jacks mtd 30" above
floor
PNC 35
Noise criteria
42 dB
Sound level
Ave coef of absorption
0.30-0.40
+45 dB
Transmission (STC)
(7) Interior Requirements
(a) Equipment
Storage for chairs and tables
12" shelves for supplies
(b) Furniture
Folding tables, stacking chairs, built-in
perimeter seating
(c) Finish Suggestions
4-24