UFC 4-740-16
25 May 2005
TABLE 3-3. SERVER ROOM
In larger facilities, the location of all the servers necessary to operate the Computer
Description/
Room. Provide direct access to Computer Room.
Usage
2.44 m (8 ft.) minimum.
Min. Ceiling Ht.
Walls. Painted gypsum wallboard.
Floor. Anti-static, non-conductive vinyl tile w/ vinyl or rubber base.
Ceiling. None required. Cable tray.
None required.
Plumbing
20 C (68 F) minimum, 26 C (78 F) maximum with 24/7 operation.
HVAC
Building system.
Fire Protection
Power
Provide dedicated, grounded, convenience outlets for each server and monitor.
Provide power for UPS system and one additional power outlet for cleaning and
maintenance.
Low level, non-glare task lighting as necessary.
Lighting
CCTV. None required.
Communication
CATV/Internal Video. None required.
PA/Audio. Provide a speaker.
Telephone. Backboard for facility. Provide one line.
Data. Provide high-speed (T1 recommended) line to serve facility.
Security. Extend partitions from finished floor to underside of structure above. Seal
around all penetrations. Lockable entrance/exit door.
Standing countertop for monitors.
Casework
Computer racks, UPS system, and stools.
Furnishings
Fixtures &
Equipment
(FF&E)
Plywood backing over gypsum wallboard for telephone backboards and UPS system.
Special
Requirements
3-3