MIL-HDBK-1005/9A
failure conditions. Telemetering should be considered for large
or remote stations or for locations where failure to react to
alarm condition could cause substantial damage.
2.5.3.9
Maintenance Considerations. For pumps and mechanical
equipment, provide access for repair and means for removal.
Facilitate maintenance and repair by planning for quick removal
of vertical pumps installed in the wet well.
2.5.3.10 Equipment and Appurtenances.
Refer to
MIL-HDBK-1005/8.
2.5.3.11 Cold Regions Design. For design criteria in cold
regions, refer to Department of Army Corps of Engineers TM
5-852.
2.5.4
Special Requirements for Pier and Wharf Systems. For
collection systems pertaining specifically to piers and wharfs,
refer to MIL-HDBK-1005/8.
2.5.5
Innovative Collection Systems. Vacuum sewers and
pressure sewers are included in this category. Refer to
MIL-HDBK-1005/8 for discussion on applications of these
innovative collection systems. A case by case determination of
specific application to industrial and oily waste should be
performed.
2.5.6
Aircraft and Vehicle Washracks, Maintenance, and
Service Areas. Washrack, maintenance, and service areas require
special attention as discussed below.
2.5.6.1
Housekeeping
a) Keep outdoor maintenance surfaces clean by regular
flushings during dry weather (pass these flushings to the
industrial sewer if available).
b) When outdoor washracks or maintenance areas are
not being used, and just before it begins to rain, close the
sluice gate in the diversion chamber so that storm runoff flows
into the storm sewer system.
34