UFC 3-530-01
22 August 2006
OFFICES
Open Offices
Pendant mounted
direct/indirect luminaires
selected and located to
A
prevent direct and
reflected glare.
north and south facades
and control glare. Integrate
lighting system where
appropriate.
Undercabinet task lights
increase illuminance on
B
desks.
EQUIPMENT RECOMMENDATIONS:
LUMINAIRE
LAMP
CONTROLS
Pendant mounted linear fluorescent,
4' linear fluorescent T8,
Daylight dimming or
A
indirect / direct luminaire, mounted
T5HO lamps 3500K color
switching. Manual dimming
0.5 0.9m (18" 36") below ceiling.
temperature, 75 CRI +
over workstations is also
(There are some luminaires available
available. Consider the use
for ceiling heights of 8' with short
of occupancy sensors for
pendants.)
cubicle groups.
Under cabinet task lighting designed
2', 3', and 4' linear
Manual on/off or on local
B
fluorescent T8 lamps 3500K
occupancy sensor.
color temperature, 75 CRI +
6-10